<Holding Register Number List (Frequency Reference and Trip Monitor)>
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolution
0001h
Output frequency setting/monitor
F001
(HIGH)
R/W
0.00 to 400.00
(Enabled when A001 = 03)
0.01
[Hz]
0002h
F001
(LOW)
R/W
0003h Inverter status A R
0: Initial status
1:
2: Stop
3: RUN
4: Free-run stop
5: Jogging
6: DC injection braking
7: Retry
8: Trip
9: During UV
0004h Inverter status B R
0: During stop
1: During RUN
2: During trip
0005h Inverter status C R
0:
1: Stop
2: Deceleration
3: Constant speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to reverse
8: Reverse to forward
9: Forward run start
10: Reverse run start
0006h PID feedback R/W 0 to 10000
0.01
[%]
0007h
to
0010h
Not used 
0011h Fault frequency monitor d080 R 0 to 65535 1 [time]
0012h Fault monitor 1 factor
d081R
See "Inverter Trip Factor List"
(page 4-183).
0013h Fault monitor 1 Inverter status
See "Inverter Trip Factor List"
(page 4-183).
0014h Fault monitor 1 frequency (HIGH)
0.00 to 400.00
0.01
[Hz]
0015h Fault monitor 1 frequency (LOW)
0016h Fault monitor 1 current
Output current value at the time of
tripping
0.1 [A]
0017h Fault monitor 1 voltage DC input voltage at the time of tripping 1 [V]
0018hFault
monitor 1 RUN time (HIGH)
Total RUN time before the trip 1 [h]
0019h Fault
monitor 1 RUN time (LOW)
001Ah Fault
monitor 1 ON time (HIGH)
Total power ON time before the trip 1 [h]
001Bh Fault monitor 1 ON time (LOW)
Note 1: The Inverter's rated current is "1000".
Note 2: If the set value is "10000" (100.0 sec) or more, the value in the second decimal place is ignored.