3-21
3-9 Parameter List
3
Operation
3-9 Parameter List
Monitor Mode (d)
•The default setting displays "d001" at power-on. To select the optional display, change the setting
in "b038".
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
d001
Output frequency
monitor
0.00 to 400.00 Yes Hz 4-1
d002
Output current
monitor
0.0 to 9999.0 A4-1
d003
Rotation direction
monitor
FWD: Forward
STOP: Stop
REV: Reverse
4-1
d004
PID feedback value
monitor
0.00 to 999000.00
(Enabled when the PID function is selected)
4-1
d005
Multi-function input
monitor
4-2
d006
Multi-function
output monitor
4-2
d007
Output frequency
monitor
(after conversion)
0.00 to 39960.00
(Output frequency × Conversion factor of b086)
Yes 4-2
d008
Real frequency
monitor
-400.00 to 400.00 Hz 4-3
d009
Torque reference
monitor
-200 to 200 %4-3
d010
Torque bias
monitor
-200 to 200 %4-3
d012
Output torque
monitor
-200 to 200 %4-3
d013
Output voltage
monitor
0.0 to 600.0 V4-3
d014 Input power monitor 0.0 to 999.9 W4-4
d015
Power ON time
monitor
0.0 to 999999.9 4-4
d016 Total RUN time 0 to 999999 h4-4
d017
Power ON time
monitor
0 to 999999 h4-4
d018
Fin temperature
monitor
-020. to 200.0 C4-4
MONITOR-A M1-STOP ALL
d005 Input
HLHLLLLHH
H001 00:OFF
1
2
3
4
5
6
7
8
FW
Example
FW, Multi-function input terminals 7, 2, 1: ON
Multi-function input terminals 8, 6, 5, 4, 3: OFF
MONITOR-A M1-STOP ALL
d006 Output
LLLLHH
H001 00:OFF
11
12
13
14
15
AL2
Example
Multi-function output terminals 12, 11: ON
Relay output terminal AL2, Multi-function
output terminals 15, 14, 13: OFF