3-32
3-9 Parameter List
3
Operation
Momentary power interruption/Trip restart
b001 Retry selection
00: TRIP (Alarm)
01: 0 Hz start
02: f-match (Frequency matching start)
03: f-match Trip (Trip after frequency
matching deceleration stop)
04: Actv. f-match (Active Frequency Matching
restart)
00 No
4-42
b002
Allowable momentary
power interruption
time
0.3 to 25.0 1.0 No s
b003 Retry wait time 0.3 to 100.0 1.0 No s 4-87
b004
Momentary power
interruption/
undervoltage trip
during stop selection
00: OFF (Disabled)
01: ON (Enabled)
02: Decel-OFF (Disabled during stop and
deceleration stop)
00 No
4-42
b005
Momentary power
interruption retry time
selection
00: 16 times
01: No limit
00 No
Momentary power interruption/Trip restart
b006
Input phase loss
protection selection
00: OFF (Disabled)
01: ON (Enabled)
01 No 4-46
b007
Frequency matching
lower limit frequency
setting
0.00 to 400.00 0.00 No Hz
4-42
4-71
4-87
b008 Trip retry selection
00: TRIP (Alarm)
01: 0 Hz start
02: f-match (Frequency matching start)
03: f-match Trip (Trip after frequency
matching deceleration stop)
04: Actv. f-match (Active Frequency Matching
restart)
00 No
4-42
b009
Undervoltage retry
time selection
00: 16 times
01: No limit
00 No
4-42
b010
Overvoltage/
overcurrent retry time
selection
1 to 3 3 No Time
b011 Trip retry wait time 0.3 to 100.0 1.0 No s
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.