EasyManua.ls Logo

Omron 3G3RX - Warning Monitor [D090]; DC Voltage Monitor [D102]; Regenerative Braking Load Rate Monitor [D103]; Electronic Thermal Monitor [D104]

Omron 3G3RX
452 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-7
4-1 Monitor Mode
4
Functions
Fault Monitors 1 to 6 [d081] to [d086]
Refer to 7. Trip Mode in
Chapter 3.4 Operation.
Warning Monitor [d090]
If the set data is inconsistent with other data, a warning code is displayed.
While this warning remains in effect, the Warning LED indicator stays lit until forced to rewrite or
correct the data.
For details on the Warning display, refer to "5-2 Warning Function".
Display: 0 to 385
DC Voltage Monitor [d102]
Displays the DC voltage (between P and N) of the Inverter.
During operation, the monitor value changes depending on the actual DC voltage of the Inverter.
(Display)
0.0 to 999.9: Displays in increments of 0.1 V.
Regenerative Braking Load Rate Monitor [d103]
Displays a regenerative braking load rate. When the monitor value comes close to exceeding the
value set in usage rate of the regenerative braking function b090, "E06 (Braking resistor overload
protection)" works to trip the Inverter.
(Display)
0.0 to 100.0: Displays in increments of 0.1%.
Electronic Thermal Monitor [d104]
Displays an electronic thermal load rate. When the monitor value comes close to exceeding 100%,
"E05 (Overload protection)" works to trip the Inverter.
(Display)
0.0 to 100.0: Displays in increments of 0.1%.

Table of Contents

Other manuals for Omron 3G3RX

Related product manuals