4-25
4-2 Function Mode
4
Functions
DC Injection Braking Carrier Frequency
You can set a DC injection braking carrier frequency in A059. Note that setting a 5 kHz or higher
frequency automatically reduces the braking power. Refer to the following figure (DC injection
braking power limit).
DC Injection Braking Power Limit
External DC Injection Braking
Allocate 07 (DB) to any of multi-function inputs C001 to C008.
DC injection braking can be applied by turning on/off the DB terminal, regardless of DC injection
braking selection A051.
Set a braking power level in DC injection braking power A054.
If DC injection braking delay time A053 is set, the Inverter output is shut off during the set time
period and the motor goes into free-run status. After the set time elapses, DC injection braking
starts.
Set DC injection braking time A055 via the Digital Operator or the DB terminal while taking into
account motor heat generation.
Perform each setting according to your system after setting DC injection braking method selection
A056.
10
9
8
7
6
5
4
3
2
1
3 5791113 15
(75)
(46)
(34)
(22)
(10)
Max.
braking power
DC injection braking carrier frequency
(a) Edge operation (A056: 00) (b) Level operation (A056: 01)
(Example 1-a) (Example 1-b)
(Example 2-a) (Example 2-b)
FW
DB
Output
frequency
A055
FW
DB
Output
frequency
FW
DB
Output
frequency
A055
FW
DB
Output
frequency