6-3
6-1 Inspection and Maintenance
6
Inspection and Maintenance
Daily Inspection and Periodic Inspection
Inspection
part
Inspection
item
Inspection point
Inspection period
Inspection method Criteria Meter
Daily
Periodic
1 year 2 years
General
Ambient
environment
Check ambient
temperature, as
well as humidity
and dust levels.
Refer to "2-1
Installation".
Ambient
temperature
10C to 50C,
no freezing.
Ambient
humidity 90%
max., no
condensation.
Thermomet
-er
Hygrometer
Recorder
Entire device
Check that there
are no abnormal
vibrations or
sounds.
Visual or acoustic
inspection
No faults
Power
supply
voltage
Check that the
main circuit
voltage is normal.
Measure the voltage
between Inverter
main circuit terminals
R/L1, S/L2, and T/L3.
Must be within
allowable
fluctuation of
AC voltage.
Tester,
digital
multimeter
Main
circuit
General
Megger check
(between main
circuit terminal
and ground
terminal)
Disconnect the I/O
wirings of the Inverter
main circuit terminal
block, detach the
control terminal block
board, and remove
the short-circuit bar
used for switching the
Inverter built-in filter
function. Then, use a
megger to measure
the resistance
between the ground
terminal and the
short-circuited parts
of terminals R/L1, S/
L2, T/L3, U/T1, V/T2,
W/T3, P/+, PD/+1,
N/-, RB, Ro, and To.
5 M min.
500 V DC
megger
*1. The life of the smoothing capacitor depends on ambient temperature.
Refer to "Appendix-2 Product Life Curve" for the replacement reference.
*2. The life of the cooling fan varies depending on the environmental conditions, such as ambient temperature
and/or dust. Check the operation through daily inspections.
*3. The replacement reference (year/cycle) or "
Appendix-2 Product Life Curve" is based on the expected design
life, which is not guaranteed.