3-47
3-9 Parameter List
3
Operation
Adjustment
C081 O adjustment 0 to 65535
Factory
default
Yes 
C082 OI adjustment 0 to 65535
Factory
default
Yes 
C083 O2 adjustment 0 to 65535
Factory
default
Yes 
C085
Thermistor
adjustment
0.0 to 1000.0
Factory
default
Yes 4-75
C091
Debug mode
selection
Use "00".
* Do not change.
00 No 
Others
C101 UP/DWN selection
00: Not save (Do not store the frequency
data)
01: Save (Store the frequency data)
00 No 4-90
C102 Reset selection
00: ON-RESET (Trip reset at power-on)
01: OFF-RESET (Trip reset when the power
is OFF)
02: On in Trip (Enabled only during trip (Reset
when the power is ON))
03: Trip RESET (Trip reset only)
00 Yes
4-87
4-137
C103
Reset frequency
matching selection
00: 0 Hz start
01: f-match (Frequency matching start)
02: Actv, f-match (Active Frequency Matching
restart)
00 No 4-87
Meter adjustment
C105 FM gain setting 50 to 200 100 Yes % 4-110
C106 AM gain setting 50 to 200 100 Yes %
4-111
C107 AMI gain setting 50 to 200 100 Yes %
C109 AM bias setting 0 to 100 0 Yes %
C110 AMI bias setting 0 to 100 20 Yes %
Terminal
C111
Overload warning
level 2
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
Rated
current
No A 4-49
Adjustment
C121 O zero adjustment 0 to 65535
Factory
default
Yes
C122 OI zero adjustment 0 to 65535
Factory
default
Yes
C123 O2 zero adjustment 0 to 65535
Factory
default
Yes
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.