App-1
Appendix-1 Parameter List
Appendix
AppAppendix
Appendix-1 Parameter List
Monitor Mode (d)
The default setting displays "d001" at power-on. To select the optional display, change the setting
in "b038".
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
d001
Output frequency
monitor
[Output FQ]
0.00 to 400.00 Yes Hz 4-1
d002
Output current
monitor
[Output current]
0.0 to 9999.0  A4-1
d003
Rotation direction
monitor
[Rotation]
FWD: Forward
STOP: Stop
REV: Reverse
4-1
d004
PID feedback value
monitor
[PID-FB]
0.00 to 999000.00
(Enabled when the PID function is selected)
4-1
d005
Multi-function input
monitor
[Input]
4-2
d006
Multi-function
output monitor
[Output]
4-2
d007
Output frequency
monitor
(after conversion)
[Scaled FQ]
0.00 to 39960.00
(Output frequency x Conversion factor of b086)
Yes 4-2
d008
Real frequency
monitor
[Actual FQ]
-400.00 to 400.00 Hz 4-3
d009
Torque reference
monitor
[Torque command]
-200 to 200 %4-3
d010
Torque bias
monitor
[Torque bias]
-200 to 200 %4-3
d012
Output torque
monitor
[Output Torque]
-200 to 200 %4-3
d013
Output voltage
monitor
[Output Voltage]
0.0 to 600.0  V4-3
MONITOR-A M1-STOP ALL
d005 Input
HLHLLLLHH
H001 00:OFF
1
2
3
4
5
6
7
8
FW
Example
FW, Multi-function input terminals 7, 2, 1: ON
Multi-function input terminals 8, 6, 5, 4, 3: OFF
MONITOR-A M1-STOP ALL
d006 Output
LLLLHH
H001 00:OFF
11
12
13
14
15
AL2
Example
Multi-function output terminals 12, 11: ON
Relay output terminal AL2, Multi-function
output terminals 15, 14, 13: OFF