4-2
4-1 Monitor Mode
4
Functions
Multi-function Input Monitor [d005]
This monitor indicates the input status of the multi-function input terminals.
The item that the built-in CPU recognizes to be "significant" is indicated as being ON.
This does not depend on the NO/NC contact setting.
(Example)
FW, Multi-function input terminals 7, 2, 1: ON
Multi-function input terminals 8, 6, 5, 4, 3: OFF
Multi-function Output Monitor [d006]
This monitor indicates the output status of the multi-function output terminals.
This monitor displays the output status of the built-in CPU, not the control circuit terminal status.
(Example)
Multi-function output terminals 12, 11: ON
Relay output terminal AL2, Multi-function output terminals 15, 14, 13: OFF
Output Frequency Monitor (After Conversion) [d007]
Displays a gain conversion value based on the coefficient set in frequency conversion coefficient
b086. This monitor is used to change the unit of displayed data (e.g. motor rpm).
"d007 display" = "Output frequency (d001)" × "Frequency conversion coefficient (b086)"
(b086) 0.1 to 99.9 (Can be set in increments of 0.1.)
(Example)
To display 4-pole motor rpm:
Motor rpm N (min
-1
) = (120 × f (Hz)) / P (pole)
= f (Hz) × 30
As such, when b086 = 30.0, a motor rpm of 1800 (60 × 30.0) is displayed.
(Display)
0.00 to 39960.00: Displays in increments of 0.01.
MONITOR-A M1-STOP ALL
d005 Input
HLHLLLLHH
H001 00:OFF
1
2
3
4
5
6
7
8
FW
MONITOR-A M1-STOP ALL
d006 Output
LLLLHH
H001 00:OFF
11
12
13
14
15
AL2