4-19
4-2 Function Mode
4
Functions
Jogging Stop Selection
Note: To perform the jogging operation, turn on the JG terminal before the FW or RV terminal.
(Do the same if the RUN command source is set to the Digital Operator.)
Torque Boost
Compensates for the voltage drop caused by the primary resistance of the motor, or by wiring to
suppress torque reduction at a low speed range.
To select the automatic torque boost for A041/A241, set motor capacity selection H003/H203 and
motor pole number selection H004/H204 according to your motor.
* To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it
on.
(Example 1) (Example 2)
With jogging stop selection A039 set to "00", "01", or
"02", jogging does not function if the FW signal is turned
on first.
With A039 set to "03", "04", or "05", jogging functions even
if the FW signal is turned on first. However, if the JG signal
is turned off before the FW signal, the motor coasts to a free
running stop.
JG
FW
Output
frequency
JG
FW
Output
frequency
Normal
operation
Deceleration
Jogging operation
Free running
Accelerates according to the b088 setting
Parameter No. Function name Data Default setting Unit
A041 Torque boost selection
00: Manual torque boost
01: Automatic torque boost
00
A241 *2nd torque boost selection
A042 Manual torque boost voltage
0.0 to 20.0
(Ratio to the value of AVR voltage
selection A082)
1.0 %A242
*2nd manual torque boost
voltage
A342 *3rd manual torque boost voltage
A043 Manual torque boost frequency
0.0 to 50.0
(Ratio to base frequency)
5.0 %
A243
*2nd manual torque boost
frequency
A343
*3rd manual torque boost
frequency
H003 Motor capacity selection
0.20 to 160.0
(Ratio to base frequency)
Factory
default
kW
H203 *2nd motor capacity selection
H004 Motor pole number selection
2/4/6/8/10 4 Pole
H204
*2nd motor pole number
selection