4-95
4-2 Function Mode
4
Functions
Multi-function Output Terminal Selection
You can allocate the following functions to any of multi-function output terminals 11 to 15 (C021 to
C025) or the alarm relay output terminal (C026).
Multi-function output terminals 11 to 15 provide open-collector output. The alarm relay output
terminal provides relay output.
You can select NO- or NC-contact output for each output terminal with C031 to C035, or C036.
If alarm code output is selected in C062 (refer to page 4-101), alarm code output (AC0 to AC3) is
provided via output terminals 11 to 13 (for 3-bit code), or via output terminals 11 to 14 (for 4-bit
code). The C021 to C025 settings are disabled.
Data Description Reference item Page
00 RUN: Signal during RUN Signal during RUN 4-98
01 FA1: Constant speed arrival signal
Frequency arrival signal 4-98
02 FA2: Over set frequency arrival signal
03 OL: Overload warning Overload limit/Overload warning 4-49
04 OD: Excessive PID deviation PID function 4-31
05 AL: Alarm output 
06 FA3: Set-frequency-only arrival signal Frequency arrival signal 4-98
07 OTQ: Overtorque Overtorque 4-100
08
IP: Signal during momentary power
interruption
Momentary power interruption/Undervoltage 4-44
09 UV: Signal during undervoltage
10 TRQ: Torque limit Torque limit function 4-57
11 RNT: RUN time over RUN time over 4-52
12 ONT: Power ON time over Power ON time over 4-52
13 THM: Thermal warning Electronic thermal function 4-46
19 BRK: Brake release
Brake control function 4-76
20 BER: Brake error
21 ZS: 0-Hz signal 0-Hz detection signal 4-101
22 DSE: Excessive speed deviation V2 control mode selection 4-124
23 POK: Position ready Orientation function 4-134
24 FA4: Set frequency exceeded 2
Frequency arrival signal 4-98
25 FA5: Set frequency only 2
26 OL2: Overload warning 2 Overload limit/Overload warning 4-49
27 ODc: Analog O disconnection detection
Window comparator function 4-6628 OIDc: Analog OI disconnection detection
29 O2Dc: Analog O2 disconnection detection
31 FBV: PID FB status output PID function 4-31
32 NDc: Network error Network error 4-104