4-2 Function Mode
4
Functions
Binary Operation
By allocating 02 to 05 (CF1 to CF4) to any of multi-function inputs 1 to 8 (C001 to C008), you can
select from multi-step speeds 0 to 15.
Use A021 to A035 (multi-step speeds 1 to 15) to set frequencies for speeds 1 to 15.
When the Digital Operator is selected as the frequency reference, speed 0 is set with A020/A220/
A320 or F001 (refer to page 4-8). When the control circuit terminal block is selected, speed 0 is set
with terminals O, O2, and OI.
For multi-step speed binary operation, you can set the
wait time until which the terminal input is
determined in multi-step speed/position determination time C169. This prevents the transition status
before the input determination from being applied.
If no input is made after the time set in C169, the data is determined.
(Note that the longer the determination time, the slower the input response.)
Multi-step speeds CF4 CF3 CF2 CF1
0th
OFF
OFF
OFF
OFF
1st ON
2nd
ON
OFF
3rd ON
4th
ON
OFF
OFF
5th ON
6th
ON
OFF
7th ON
8th
ON
OFF
OFF
OFF
9th ON
10th
ON
OFF
11th ON
12th
ON
OFF
OFF
13th ON
14th
ON
OFF
15th ON
CF1
CF2
CF3
CF4
FW
1st
2nd
3rd
4th
5th
6th
7th
8th
9th
10th
11th
12th
13th
14th
15th
0th
Frequency from
the Digital Operator
or the external
analog input terminal
Determination
time (C169)
CF1
CF2
CF3
Frequency reference
13
1
5
9
Without determination time (C169)
11
CF4
15
With determination time (C169)
4