4-2 Function Mode
4
Functions
Special Reduced Torque Characteristics (Special VP)
Suitable for a fan or pump that requires torque in a low speed range. These have VC characteristics
only for low deceleration in reduced torque characteristics.
Period a: Provides constant torque characteristics within a range from 0 Hz to 10% of the base
frequency.
(Example) If the base frequency is 50 Hz, the Inverter provides constant torque
characteristics within a range from 0 to 5 Hz.
Period b: Provides reduced torque characteristics within a range from 10% to 100% of the base
frequency.
The Inverter outputs voltage based on a curve of the 1.7th power of the frequency.
Period c: Provides constant voltage characteristics within a range from the base frequency to the
maximum frequency.
Free V/f Setting
You can set desired V/f characteristics by setting 7 points of voltage and frequency. (b100 to b113)
The free V/f frequencies should always be 1 2 3 4 5 6 7.
All the default settings are 0 Hz. You must set Free V/f setting 7 first. (Operation is disabled by
factory default.)
If the free V/f setting is enabled, the functions of torque boost A041/A241, base frequency A003/
A203/A303, and maximum frequency A004/A204/A304 are disabled. (Free V/f frequency 7 is
regarded as the maximum frequency.)
0
Output
voltage
(100%)
Base
frequency
Output
frequency (Hz)
Max.
frequency
VC
VP(f )
10% of base
frequency
1.7
a
b
c
Parameter No. Function name Data Description Default setting Unit
b100 Free V/f frequency 1 0 to Free V/f frequency 2
Set frequencies for
each break point.
0Hz
b102 Free V/f frequency 2 0 to Free V/f frequency 3
b104 Free V/f frequency 3 0 to Free V/f frequency 4
b106 Free V/f frequency 4 0 to Free V/f frequency 5
b108 Free V/f frequency 5 0 to Free V/f frequency 6
b110 Free V/f frequency 6 0 to Free V/f frequency 7
b112 Free V/f frequency 7 0 to 400
b101 Free V/f voltage 1
0.0 to 800.0
Set output voltages
for each break point.
*
0.0 V
b103 Free V/f voltage 2
b105 Free V/f voltage 3
b107 Free V/f voltage 4
b109 Free V/f voltage 5
b111 Free V/f voltage 6
b113 Free V/f voltage 7
Related functions A044, A244, A344