3-33
3-9 Parameter List
3
Operation
Electronic Thermal
b012
Electronic thermal
level
0.20 × Rated current to 1.00 × Rated current
Rated
current
No A
4-46
b212
* 2nd electronic
thermal level
b312
* 3rd electronic
thermal level
b013
Electronic thermal
characteristics
selection
00: Reduced TRQ (Reduced torque
characteristics)
01: Const TRQ (Constant torque
characteristics)
02: Free set (Free setting)
00 No
b213
* 2nd electronic
thermal
characteristics
selection
b313
* 3rd electronic
thermal
characteristics
selection
b015
Free setting,
electronic thermal
frequency 1
0 to 400 0 No Hz
4-46
b017
Free setting,
electronic thermal
frequency 2
b019
Free setting,
electronic thermal
frequency 3
b016
Free setting,
electronic thermal
current 1
0.0 to Rated current 0.0 No Ab018
Free setting,
electronic thermal
current 2
b020
Free setting,
electronic thermal
current 3
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.