3-50
3-9 Parameter List
3
Operation
Control parameter
H001 Auto-tuning selection
00: OFF (Disabled)
01: ON (STOP)
02: ON (Rotation)
00 No 4-111
H002
Motor parameter
selection
00: Standard motor parameter
01: Auto-tuning parameter
02: Auto-tuning parameter
(online auto-tuning enabled)
00
No
4-111
4-113
4-115
H202
* 2nd motor
parameter selection
00
H003
Motor capacity
selection
0.20 to 160.0
Factory
default
No kW
4-19
4-111
4-115
4-118
H203
* 2nd motor capacity
selection
Factory
default
H004
Motor pole number
selection
2/4/6/8/10
4
No Pole
H204
* 2nd motor pole
number selection
4
H005 Speed response
0.001 to 80.000
1.590
Yes
4-89
4-92
H205 * 2nd speed response 1.590
H006
Stabilization
parameter
0 to 255
100
Yes 4-120H206
* 2nd stabilization
parameter
100
H306
* 3rd stabilization
parameter
100
H020 Motor parameter R1
0.001 to 65.535
Depends
on the
motor
capacity.
No
4-115
H220
* 2nd motor
parameter R1
Depends
on the
motor
capacity.
H021 Motor parameter R2
0.001 to 65.535
Depends
on the
motor
capacity.
No
H221
* 2nd motor
parameter R2
Depends
on the
motor
capacity.
H022 Motor parameter L
0.01 to 655.35
Depends
on the
motor
capacity.
No mH
H222
* 2nd motor
parameter L
Depends
on the
motor
capacity.
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001