3-18
3-7 Part Names and Descriptions of the Digital Operator
3
Operation
Display System and Key Sequence of Each Code
• This section explains the examples of typical operation (Basic display, Complete display) and the
extended function mode U as a special operation.
This operation can be performed when other display modes are selected.
Note: The Digital Operator display varies depending on the settings of display selection "b037", ini-
tial screen selection "b038", and user parameter automatic setting function selection "b039".
For details, refer to "Display Selection" (page 4-53), "Initial Screen Selection (Initial Screen
at Power-ON)" (page 4-56), "User Parameter Automatic Setting Function" (page 4-57).
UP key
It is used to move up the cursor, it increases a function code in
1 or increases a parameter value.
DOWN key
It is used to move down the cursor, it decreases a function code
in 1 or it decreases a value.
PREV. PAGE key
It is used to move the cursor to the left, or it moves to previous
mode when the display is a navigation level.
NEXT PAGE key
It is used to move the cursor to the right, or it moves to the next
mode when the display is a navigation level.
FWD RUN key
It is used to run forward the motor only when the operation
command (A002) is reset in Digital operator.
REV RUN key
It is used to run reverse the motor only when the operation
command (A002) is set in Digital operator.
STOP/RESET key
It is used to stop the motor or reset an alarm. It is also possible
to invalidate the STOP key by B087 parameter. Besides it does
not response when LCD digital operator is reading or writing the
parameters from/to the inverter.
Name Function
The display indicates the setting of "b038" when the power is turned on. For details, refer to
"Initial Screen Selection (Initial Screen at Power-ON)" (page 4-56).
When "b038 = 1" (factory default), output frequency monitor "d001" is displayed.
Item Function code Data Description
Display selection b037
00 Complete display (factory default)
01 Individual display of functions
02 User setting
03 Data comparison display
04 Basic display
Initial screen
selection
(Power On)
b038
000 Screen when the Enter key was pressed last
001-060 d001-d060 displayed
201 F001 (Output frequency setting/monitor)
202 Monitor screen
User parameter
automatic setting
function selection
b039
00 Disabled (factory default)
01 Enabled