4-5
4-1 Monitor Mode
4
Functions
Motor Temperature Monitor [d019]
•Displays the temperature of the thermistor connected between the control circuit terminals TH and
CM1.
•Set thermistor selection b098 to "02" (NTC enabled).
(Display)
-020. to 200.0: Displays in increments of 0.1C.
Note: When b098 = "01" (PTC enabled), the motor temperature monitor is disabled.
Life Assessment Monitor [d022]
•This monitor indicates a life assessment result.
The following two items can be monitored:
1: Main circuit board capacitor service life
2: Cooling fan rpm reduction
Note 1: The capacitor service life is calculated every 10 minutes. If the Inverter is turned on/off
frequently within this interval, the capacitor service life cannot be correctly diagnosed.
Note 2: While the cooling fan is stopped with b092 set to "01", the cooling fan rpm is judged as being
normal.
Program Counter [d023]
Refer to Drive Programming Manual.
Display: 0 to 1024
Program Number [d024]
Refer to Drive Programming Manual.
Display: 0 to 9999
Drive Programming Monitor (UM0 to UM2) [d025 to d027]
Refer to Drive Programming Manual.
Display: -2147483647 to 2147483647
MONITOR-A M1-STOP ALL
d022 Life(C/F)
LL
H001 00:OFF
1
2