4-179
4-4 Communication Function
4
Functions
0044h MO6 (Drive Programming output 6) R/W
1: ON
0: OFF
0045h IRDY (operation ready signal) R
1: ON
0: OFF
0046h FWR (forward run signal) R
1: ON
0: OFF
0047h RVR (reverse run signal) R
1: ON
0: OFF
0048h MJA (fatal fault signal) R
1: ON
0: OFF
0049h During data write R
1: Writing
0: Normal
004Ah CRC error R
1: Error
0: No error
*2
004Bh Overrun error R
1: Error
0: No error
*2
004Ch Framing error R
1: Error
0: No error
*2
004Dh Parity error R
1: Error
0: No error
*2
004Eh Checksum error R
1: Error
0: No error
*2
004Fh Not used
0050h
WCO
(window comparator O)
R
1: ON
0: OFF
0050h
WCOI
(window comparator OI)
R
1: ON
0: OFF
0052h
WCO2
(window comparator O2)
R
1: ON
0: OFF
Coil No. Item R/W Description
*1. When either the control circuit terminal block or the coil is turned on, these settings are ON.
The control circuit terminal block has the priority for the multi-function input terminals.
If the master cannot reset the coil ON status because of communication disconnection, turn the control
circuit terminal block from ON to OFF to turn off the coil.
*2. The communications error is retained until a fault reset is input. (Can be reset during operation.)