4-50
4-2 Function Mode
4
Functions
Increase the overload limit level (b022/b025).
Overload Warning
If the applied load is large, the Inverter can output an overload warning signal before an overload
trip occurs.
This helps prevent mechanical damage due to an overload in the carrier machine, or an operation
line stop due to overload protection of the Inverter.
Allocate "03" (OL) or "26" (OL2) to any of multi-function output terminals 11 to 15 (C021 to C025)
or the relay output terminal (C026). (Two types of overload warning signals are available for
output.)
Overload limit level
b022/b025
Output current
Max. frequency
A004/A204/A304
Inverter output
frequency
b023/b026
Decelerates according to the set
overload limit parameter.
Target frequency
F001
Overload limit level
b022/b025
Overload warning level
C041/C111
Output current
OL/OL2 output