4-67
4-2 Function Mode
4
Functions
•You can set hysteresis widths for the window comparator upper and lower limit levels.
•You can set limit levels and a hysteresis width individually for O, OI, and O2 inputs.
•For the WCO/WCOI/WCO2 output, you can fix the analog input application value to the desired
value. Set values in O/OI/O2 disconnection operation levels b070/b071/b072. If "no" is set, the
analog input value is directly reflected.
•ODc/OIDc/O2Dc outputs are the same as WCO/WCOI/WCO2, respectively.
b062 (O)
Window comparator
O/OI/O2 hysteresis width
Set a hysteresis width for the upper and lower
limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
0%
b065 (OI)
b068 (O2)
b070 (O)
Analog operation level at
O/OI/O2 disconnection
0 to 100/no (ignored): Set an analog input
application value used for WCO/WCOI/
WCO2 (ODc/OIDc/O2Dc) output.
no
b071 (OI)
b072 (O2)
-100 to 100/no (ignored): Set an analog input
application value used for WCO/WCOI/
WCO2 (ODc/OIDc/O2Dc) output.
Parameter No. Function name Data Default setting Unit
WCO/WCOI/WCO2
ODc/OIDc/O2Dc
Max (100%)
Min (O/OI: 0%)
(O2
: -100%)
O/OI/O2 inputs
Analog application value
Analog input value
Analog operating level on
disconnection
(b070/b071/b072)
Window comparator upper
limit level (b061/b064/b067)
Window comparator lower
limit level (b060/b063/b066)
Hysteresis width
(b062, b065, b068)