4-69
4-2 Function Mode
4
Functions
If the above maximum rated carrier frequency and the derating value at 15 kHz are exceeded, the
Inverter may be damaged and/or the service life may be shortened.
7.5 kW 15 100% 100% 15 100% 100%
11 kW 12 90% 90% 15 100% 100%
15 kW 12 90% 95% 14 100% 95%
18.5 kW 10 90% 90% 10 95% 90%
22 kW 7 90% 70% 6 90% 75%
30 kW 5 80% 80% 10 80% 75%
37 kW 10 75% 75% 8 90% 80%
45 kW 5 90% 70% 9 80% 75%
55 kW 5 90% 70% 6 75% 60%
75 kW  690% 85%
90 kW  4 80% 75%
110 kW  6 80% 70%
132 kW  3 70% 60%
Voltage 200-V class 400-V class
Capacity
Max. fc
(kHz)
Derating at fc =
12 kHz (ND)
Derating at fc =
15 kHz (HD)
Max. fc
(kHz)
Derating at fc =
12 kHz (8kHz
for 75 to 132
kW) (ND)
Derating at fc =
15 kHz (10 kHz
for 75 to 132 kW)
(HD)
60
55
100
95
90
85
80
75
70
65
37kW
18.5kW
0.5
2
4
6
8
10
12
45kW
0.4-2.2kW,
5.5-15kW
22kW
30kW
55kW
75kW
90kW
110kW
132kW
4.0kW
60
55
100
95
90
85
80
75
70
65
11kW
15kW,45kW
0.5
2
4
6
8
10
12
22kW
0.4-2.2kW,
5.5kW, 7.5kW
30kW
3.7kW,18.5kW
37kW
55kW
Normal duty
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
200-V class 400-V class
Output current derating
Carrier frequency (kHz)
Output current derating
Carrier frequency (kHz)
15 kW
37 kW
30 kW
11 kW
18.5 kW
22 kW
45, 55 kW
15 kW
22 kW
18.5 kW
37 kW
55 kW
30 kW
75 kW
90 kW
110 kW
132 kW
45 kW
Heavy duty
Output current derating
Output current derating
Carrier frequency (kHz)
Carrier frequency (kHz)
400-V class
200-V class