4-69
4-2 Function Mode
4
Functions
•If the above maximum rated carrier frequency and the derating value at 15 kHz are exceeded, the 
Inverter may be damaged and/or the service life may be shortened.
7.5 kW 15 100% 100% 15 100% 100%
11 kW 12 90% 90% 15 100% 100%
15 kW 12 90% 95% 14 100% 95%
18.5 kW 10 90% 90% 10 95% 90%
22 kW 7 90% 70% 6 90% 75%
30 kW 5 80% 80% 10 80% 75%
37 kW 10 75% 75% 8 90% 80%
45 kW 5 90% 70% 9 80% 75%
55 kW 5 90% 70% 6 75% 60%
75 kW   690% 85%
90 kW   4 80% 75%
110 kW   6 80% 70%
132 kW   3 70% 60%
Voltage 200-V class 400-V class
Capacity
Max. fc 
(kHz)
Derating at fc = 
12 kHz (ND)
Derating at fc =     
15 kHz (HD)
Max. fc 
(kHz)
Derating at fc = 
12 kHz (8kHz 
for 75 to 132 
kW) (ND)
Derating at fc = 
15 kHz (10 kHz 
for 75 to 132 kW) 
(HD)
 
 
60
55
100
95
90
85
80
75
70
65
37kW 
18.5kW 
0.5 
2 
4 
6 
8 
10 
12 
45kW 
22kW 
30kW 
55kW 
75kW 
90kW  
110kW 
132kW 
4.0kW 
 
 
60
55
100
95
90
85
80
75
70
65
11kW 
15kW,45kW 
0.5 
2 
4 
6 
8 
10 
22kW 
0.4-2.2kW, 
5.5kW, 7.5kW 
30kW 
3.7kW,18.5kW 
37kW 
55kW
 
Normal duty
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
200-V class 400-V class
Output current derating
Carrier frequency (kHz)
Output current derating
Carrier frequency (kHz)
15 kW
37 kW
30 kW
11 kW
18.5 kW
22 kW
45, 55 kW
15 kW
22 kW
18.5 kW
37 kW
55 kW
30 kW
75 kW
90 kW
110 kW
132 kW
45 kW
Heavy duty
Output current derating
Output current derating
Carrier frequency (kHz)
Carrier frequency (kHz)
400-V class
200-V class