4-150
4-4 Communication Function
4
Functions
Note 1: Data is a value obtained by mulplying the set value by 100.
(Example) 5 (Hz) 500 000500 ASCII conversion 30 30 30 35 30 30
Note 2: To use the data as PID control feedback data, set "1" in the MSB of the data.
(Example) 5 (%) 500 100500 ASCII conversion 31 30 30 35 30 30
•Response frame
Normal response: Refer to page 4-161.
Error response: Refer to page 4-161.
<Command 02>
Sets multi-function input terminal status.
•Transmission frame
Frame format
STX Station No. Command Data BCC CR
Description Data size Setting
STX Control code (Start of TeXt) 1 byte STX (0x02)
Station No. Station No. of the target Inverter 2 bytes
01 to 32, and FF (Communication with
all stations)
Command Transmission command 2 bytes 02
Data Transmission data 16 bytes *
BCC Block check code 2 bytes
Exclusive OR from station No. to data.
(Refer to page 4-163.)
CR Control code (Carriage Return) 1 byte CR (0x0D)