4-153
4-4 Communication Function
4
Functions
Response frame
Positive response: Refer to page 4-161.
Negative response: Refer to page 4-161.
<Command 03>
Reads all monitor data.
Transmission frame
Response frame
Frame format
STX Station No. Command BCC CR
Description Data size Setting
STX Control code (Start of TeXt) 1 byte STX (0x02)
Station No. Station No. of the target Inverter 2 bytes 01 to 32
Command Transmission command 2 bytes 03
BCC Block check code 2 bytes
Exclusive OR from station No. to
data. (Refer to page 4-163.)
CR Control code (Carriage Return) 1 byte CR (0x0D)
Frame format
STX Station No. Data BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station No. Station No. of the target Inverter 2 bytes 01 to 32
Data Data 104 bytes *
BCC Block check code 2 bytes
Exclusive OR from station No. to
data. (Refer to page 4-163.)
CR Control code (Carriage Return) 1 byte CR (0x0D)