EasyManua.ls Logo

Omron 3G3RX - Page 319

Omron 3G3RX
452 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-200
4-4 Communication Function
4
Functions
1385h
Overvoltage protection
function selection during
deceleration
b130 R/W
00: OFF (Disabled)
01: V-const (DC voltage kept constant)
02: Accel (Acceleration enabled)
1386h
Overvoltage protection
level during deceleration
b131 R/W
200-V class: 330 to 390 (V)
400-V class: 660 to 780 (V)
1 [V]
1387h
Overvoltage protection
parameter
b132 R/W 0.10 to 30.00 0.01 [s]
1388h
Overvoltage protection
proportional gain setting
b133 R/W 0.00 to 2.55 0.01
1389h
Overvoltage protection
integral time setting
b134 R/W 0.000 to 65.535 0.001 [s]
1390h
to
1400h
Not used 
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolu-
tion