2-7
2-2 Wiring
2
Design
Continued to the next page
Analog
Monitor output
AM Multi-function analog
output
(Voltage)
This terminal outputs a signal selected from
the "0 to 10 V DC Voltage Output" monitor
items: Output frequency, Output current,
Output torque (with/without sign), Output
voltage, Input power, Electronic thermal load
rate, LAD frequency, Motor temperature,
and Fin temperature.
Allowable max. current:
2 mA
AMI Multi-function analog
output
(Current)
This terminal outputs a signal selected from
the "4 to 20 mA DC Current Output" monitor
items: Output frequency, Output current,
Output torque (without sign), Output voltage,
Input power, Electronic thermal load rate,
LAD frequency, Motor temperature, and Fin
temperature.
Allowable load
impedance:
250 max.
Digital (contact)
Monitor output
FM Multi-function digital
output
This terminal outputs a signal selected from
the "0 to 10 V DC Voltage Output (PWM)"
monitor items: Output frequency, Output
current, Output torque (without sign), Output
voltage, Input power, Electronic thermal load
rate, LAD frequency, Motor temperature, Fin
temperature, Digital output frequency, and
Digital current monitor.
"Digital output frequency", and "Digital
current monitor" output a digital pulse at 0/10
V DC pulse voltage and 50% duty ratio.
Allowable max. current:
1.2 mA
Max. frequency:
3.6 kHz
Power supply
P24 Internal 24 V DC 24 V DC power supply for contact input
signal.
When the source logic is selected, this
terminal functions as the contact input
common terminal.
Allowable max. output
current:
100 mA
CM1 Input common Common terminal for the interface power
supply P24 terminal, thermistor input TH
terminal and digital monitor FM terminal.
When the sink logic is selected, this terminal
functions as the contact input common
terminal. Do not connect this terminal to the
ground.
Terminal
symbol
Terminal name Description Specifications