2-18
2-2 Wiring
2
Design
*1. When the cable is connected without using the crimp terminal (bare wires), use the square washer included
with the product.
Note: The cable size is based on the HIV cable (75C heat resistance).
400-V class
0.4 3G3RX-A4004 1.25 1.25 1.25 M4 1.25-4
1.2
(max.1.8)
Fuse (Type J)
20 A
0.75 3G3RX-A4007 1.25 1.25 1.25 M4 1.25-4
1.2
(max.1.8)
20 A
1.5 3G3RX-A4015 2 2 2 M4 2-4
1.2
(max.1.8)
20 A
2.2 3G3RX-A4022 2 2 2 M4 2-4
1.2
(max.1.8)
20 A
4.0 3G3RX-A4040 2 2 2 M4 2-4
1.2
(max.1.8)
20 A
5.5 3G3RX-A4055 3.5 3.5 3.5 M5 R2-5
2.4
(4.0 max.)
Inverse time circuit Breaker
40 A
7.5 3G3RX-A4075 3.5 3.5 3.5 M5 3.5-5
2.4
(4.0 max.)
40 A
11 3G3RX-A4110 5.5 5.5 5.5 M6 R5.5-6
4.0
(4.4 max.)
40 A
15 3G3RX-A4150 88 8 M6 8-6
4.5
(4.9 max.)
75 A
18.5 3G3RX-A418514 14 14 M6 14-6
4.5
(4.9 max.)
75 A
22 3G3RX-A4220 14 14 14 M6 14-6
4.5
(4.9 max.)
75 A
30 3G3RX-A4300 22 22 - M6 22-6
4.5
(4.9 max.)
100 A
37 3G3RX-A4370 38 22 M8
*1
38-8
8.1
(20.0 max.)
100 A
45 3G3RX-A4450 38 22 M8
*1
38-8
8.1
(20.0 max.)
150 A
55 3G3RX-A4550 60 30 M8
*1
R60-8
8.1
(20.0 max.)
150 A
75 3G3RX-B4750
100
(38 x 2)
38 M10
*1
100-10
20.0
(22.0 max.)
225 A
90 3G3RX-B4900
100
(38 x 2)
38 M10
*1
100-10
20.0
(22.0 max.)
225 A
110 3G3RX-B411K
150
(38 x 2)
60 M10
*1
150-10
20.0
(35.0 max.)
300 A
132 3G3RX-B413K 80 x 2 80 M10
*1
80-10
20.0
(35.0 max.)
350 A
Motor
output
(kW)
Applicable
Inverter model
Power
cable
(mm
2
)
R, S, T,
U, V, W,
PD/+1,
P/+, N/-
Ground
cable
(mm
2
)
External
braking
resistor
between
PD/+1 and
RB (mm
2
)
Terminal
screw
size
Crimp
terminal
Tightening
torque
N•m
Circuit
break-
er or
fuse
Applicable
device
Earth
leakage
breaker
(ELB)