3-30
3-9 Parameter List
3
Operation
RUN mode, Acceleration/Deceleration functions
A092 Acceleration time 2
0.01 to 3600.00
10.00
Yes s
4-37
A292
* 2nd acceleration
time 2
10.00
A392
* 3rd acceleration
time 2
10.00
A093 Deceleration time 2 10.00
A293
* 2nd deceleration
time 2
10.00
A393
* 3rd deceleration
time 2
10.00
A094
2-step acceleration/
deceleration
selection
00: 2CH-Terminal (Switched via multi-
function input 09)
01: Preset FQ (Switched by setting)
02: FWD-REV (Enabled only when switching
forward/reverse)
00
No
A294
* 2nd 2-step
acceleration/
deceleration
selection
00
A095
2-step acceleration
frequency
0.00 to 400.00
0.00
No Hz
A295
* 2nd 2-step
acceleration
frequency
0.00
A096
2-step deceleration
frequency
0.00
No Hz
A296
* 2nd 2-step
deceleration
frequency
0.00
A097
Acceleration pattern
selection
00: Line
01: S-curve
02: U-curve
03: inv. U curve
04: EL-S curve
01 No
4-38
A098
Deceleration pattern
selection
01 No
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001