Section 10 Transferring Data 10-3 Data Transfer Using SPMA
NS-Designer Operation Manual
Set the IP address of the
PLC’s Ethernet Uniti.
10. Input the IP address of the PLC’s Ethernet Unit. Here, 192.168.0.6 is input as an example.
11. Click the OK Button in the Network Setting Dialog Box.
12. Set the Network Address between the PT and PLC (the value set in the local network table using
CX-Net). In this example, 3 was set as the Network Address for Controller Link communications
and so set 3.
13. Set the Node Address of the destination PT. In this example, set the Node Address of the PT’s
Controller Link Unit, i.e., set 5.
Set the Controller Link communications network
address (the value set for the local network table
in the CX-Net) between the PT and PLC.
Set the unit number of the PT that will be the
destination.
14. Click the OK Button.