Name Standard [(identifier) attribute]
Sup-
port
Implementation
specifications
snmpOutNoSuch-
Names
[(21) RO]
The total number of PDUs sent with an error
status of noSuchName.
Sup-
ported
According to the
standard.
snmpOutBadValues [(22) RO]
The total number of PDUs sent with an error
status of badV
alue.
Sup-
ported
According to the
standard.
snmpOutGenErrs
[(24) RO]
The total number of PDUs sent with an error
status of genErr.
Sup-
ported
According to the
standard.
snmpOutGetRequests
[(25) RO]
The total number of GetRequest PDUs sent.
Sup-
ported
According to the
standard.
snmpOutGetNexts [(26) RO]
The total number of GetNextRequest PDUs
sent.
Sup-
ported
According to the
standard.
snmpOutSetRequests [(27) RO]
The total number of SetRequest PDUs sent.
Sup-
ported
According to the
standard.
snmpOutGetResponses [(28) RO]
The total number of GetResponse PDUs sent.
Sup-
ported
According to the
standard.
snmpOutTraps [(29) RO]
The total number of trap PDUs sent.
Sup-
ported
According to the
standard.
snmpEnableAuthen-
T
raps
[(30) R
W]
Determines if the agent generates verification
failed traps.
enabled (1)
disabled (2)
Sup-
ported
According to the
standard.
l
Lldp Group
Name Standard [(identifier) attribute]
Sup-
port
Implementation
specifications
lldpConfiguration [(1) NA]
The MIB for LLDP configuration.
--- ---
lldpMessageTxInterval [(1) RW]
The LLDP frame transmission inter-
val.
Default value: 30 (seconds)
Sup-
ported
Variable value de-
pending on setting:
5 to 32,768
lldpMessageTxHoldMultiplier [(2) RW]
The value to determine TTL of the
LLDP frame, this is placed in the
LLDP frame header
.
TTL (seconds) = lldpMessageTx-
HoldMultipler × lldpMessageTxInterv-
al
However
, the maximum value of TTL
shall be 65,535 seconds.
Default value: 4
Sup-
ported
Variable value de-
pending on setting:
1 to 100
lldpReinitDelay [(3) RW]
The time until re-initialization process
is attempted when lldpPortConfigAd-
minStatus becomes “disabled”.
Default value: 2 (seconds)
Sup-
ported
Always 2.
11 SNMP Agent
11-19
NX-series EtherNet/IP Unit User's Manual (W627)
11-1 SNMP Agent
11
11-1-4 MIB Specifications

Table of Contents

Other manuals for Omron NX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX Series and is the answer not in the manual?

Omron NX Series Specifications

General IconGeneral
BrandOmron
ModelNX Series
CategoryController
LanguageEnglish

Related product manuals