Event name SNMP Setting Error Event code 36060000 hex
Meaning A setting error in SNMP agent/trap was detected.
Source X Bus Ethernet Function Module Source details 1 to 4: Mounting
position of the X
Bus Unit (unit
number)
and
SNMP
are given
in combination
Detection tim-
ing
At power ON or
Controller reset
Error attributes Level Minor fault Recovery Automatic re-
covery (after
downloading the
SNMP settings),
cycle the power
supply, or Con-
troller reset
Log category System
Effects User program Continues. Operation SNMP operation stops.
Indicators
Ethernet NET RUN Ethernet NET ERR Ethernet LINK/ACT
--- Flashes at 1-s intervals. ---
Device variable Variable Data type Name
None --- ---
Cause and cor-
rection
Assumed cause Correction Prevention
Parameter error Identify the cause of the error from
the attached information, correct
the settings, and then download
the settings again.
None
Power interruption while download-
ing SNMP agent/trap settings
Clear all memory or download the
settings again.
Do not turn OFF the power supply
to the Controller while the SNMP
agent/trap settings are being down-
loaded.
Memory error If the above measures do not work,
replace the Unit.
None
Attached infor-
mation
Attached information 1: Error type
01 hex: Non-volatile Memory Access Error
, 02 hex: There is an inconsistency in the set values.
Attached information 2: Error Location
If there is an inconsistency in the set values:
01 hex: SNMP agent settings, 02 hex: SNMP trap settings
Precautions/
Remarks
None
14 Troubleshooting
14-21
NX-series EtherNet/IP Unit User's Manual (W627)
14-4 Checking with the Sysmac Studio, an HMI, and Instructions That Read Error
Status
14