D-30 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Clone Start
1542
Same as PNO 1534
FALSE
ALWAYS
When TRUE this parameter starts the cloning process, either saving or loading depending on the parameter 1537 Clone Direction.
The cloning process will only start if the parameter 1543 Clone Status is IDLE.
Once the cloning has completed the parameter 1543 Clone Status will be DONE. Set the Clone Start parameter back to FALSE to
return to the IDLE state.
Clone Status
1543
Same as PNO 1534
0:IDLE
1:SAVING
2:RESTORING
3:VERIFYING
4:DONE
5:CANNOT START
6:FAILED
7:NO SD CARD
8:VERIFY FAILED
9:FILE NOT OPENED
10:FILE INCOMPATIBLE
11:FILE FAILURE
12:POWER MISMATCH
13:APPLICATION FAILURE
14:PARAMETERS FAILURE
NEVER
This parameter indicates the status of the cloning process.
Enumerated Value : Power Parameters
0 : IDLE - waiting for the user to start the cloning process.
1: SAVING - in the process of saving the drive configuration to file.
2 : RESTORING - in the process of loading the configuration from file.
3 : VERIFYING - in the process of verifying the clone file either before a load or after a save.
4 : DONE - the cloning process has completed successfully either for a load or a save.
5 : CANNOT START - the cloning process cannot start. When restoring a configuration the drive must be stopped.
6 : FAILED - general failure of the cloning process.
7 : NO SD CARD - no SD card is fitted.