D-96 Parameter Reference
AC30 series Variable Speed Drive
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to FALSE.
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the hardware
range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
Terminal X11.3
The desired output value expressed as a percentage of the output range.
0% gives 0V, 100% gives 10V
0% gives 0mA, 100% gives 20mA
0% gives 4mA, 100% gives 20mA
Terminal X11.4
The desired output value expressed as a percentage of the output range.
-100% gives -10V, 100% gives 10V
0% gives 0V, 100% gives 10V