Parameter Reference D-95
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Digin Value
0005
Monitor::Inputs and Outputs
Parameters::Inputs And Outputs::IO
Values
0:Digin 01
1:Digin 02
2:Digin 03
3:Digin 04
4:Digin 05
5:Digin 06
6:Digin 07
7:STO Inactive
8:Digin 11
9:Digin 12
10:Digin 13
11:Digin 14
12:Run Key
13:Not Stop Key
14:Stop Key
NEVER
Presents all the digital inputs to the drive as a 16-bit word. The bits within the word may be accessed individually, or the entire word
may be accessed as a group.
Bit
Signal name
Terminal
Comment
PNO for individual bit access
0
Digital Input 01
X13.2
0006
1
Digital Input 02
X13.3
0007
2
Digital Input 03
X13.4
0008
3
Digital Input 04
X12.1
Common terminal with digital output 1
0009
4
Digital Input 05
X12.2
Common terminal with digital output 2
0010
5
Digital Input 06
X12.3
Common terminal with digital output 3
0011
6
Digital Input 07
X12.4
Common terminal with digital output 4
0012
7
STO Inactive
X10
0013
8
Digital Input 11
X20.1
GPIO option
0014
9
Digital Input 12
X20.2
GPIO option
0015
10
Digital Input 13
X20.3
GPIO option
0016
11
Digital Input 14
X20.4
GPIO option
0017
12
Run Key
-
GKP Run key pressed*
0018
13
Not Stop Key
-
GKP Stop key not pressed*
0019
14
Stop Key
-
GKP Stop key pressed*
0020
* If the GKP is not fitted then both “Not Stop Key” and “Stop Key” will be 0. This condition may be used to detect a disconnected GKP.