EasyManua.ls Logo

REXROTH Fv Series - Page 154

REXROTH Fv Series
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3.06
Td: Derivative time Factory default 0.00
Setting range
0.00...100.00 s
(0.00 represents no derivative)
Minimum unit 0.01
E3.07
T: Sampling period Factory default 0.50
Setting range 0.01...100.00 s Minimum unit 0.01
Used to set PID control parameters.
P: Proportional gain
Used to eliminate deviation
Larger P means larger scale and faster response, but too large P
leads to oscillation.
P cannot eliminate deviation completely.
Ti: Integral time
Used to eliminate remained deviation
Smaller Ti means faster response of frequency converter to devia‐
tion changes, but too mall Ti leads to oscillation.
Td: Derivative time
Used to respond fast to changes of deviation between reference and
feedback exists in the system.
Larger Td means faster response, but too large Td leads to oscilla‐
tion.
E3.08
Deviation limit Factory default 2.0
Setting range
0.0...20.0 %
(of closed loop reference)
Minimum unit 0.1
Used to set the limit of the deviation between reference signals and feedback
signals to stop internal PID control and keep stable output.
PID control stops when feedback deviation is within the range of ‘Devia‐
tion limit’ [E3.08].
Control accuracy and stability of the system should be taken into
account in setting of parameter ‘Deviation limit’ E3.08.
E3.09
PID adjustment mode Factory default 0
Setting range 0, 1 Minimum unit 1
In closed loop PID control, if the output value reaches parameter ‘Upper fre‐
quency’ [b1.06] or ‘Lower frequency’ [b1.07], the integral loop has two op‐
tions:
0: Stop integral adjustment
The integral value remains unchanged.
When the difference between reference value and feedback value
changes, the integral value will change immediately with the
changing trend.
1: Continue integral adjustment
The integral value responds simultaneously to the difference change be‐
tween the reference value and the feedback value.
Bosch Rexroth AG DOK-RCON02-FV*********-IB08-EN-P152/259
Rexroth Frequency Converter Fv
Parameter Settings

Table of Contents