7. Internal Web pages
Issue 06/15 Publication PUB059-002-00 85 of 136
Remote selected - local remote selector in remote position.
Moving - actuator centre column moving.
Monitor Relay - monitor relay alarm.
Open Limit - open position limit switch.
Closed Limit - closed position limit switch.
Comms Failed - loss of network communication.
Thermostat - motor thermostat tripped.
Torque Tripped - torque limit level exceeded.
Manual move - actuator moved by the handwheel.
POR - power on reset.
Watchdog - field unit watchdog alarm.
AUX OR - auxiliary input present.
Start / Stop - failure to respond to a remote control input.
MemF - FCU memory chip fault.
EOT - motor running at end of travel.
Network Open - open instruction over the control network.
Network Close - close instruction over the control network.
Network Stop - stop instruction over the control network.
Network ESD - ESD instruction over the control network.
Position / Time - last position control event.
Position / Time - last but one position control event.
Position / Time - last but two position control event.
Controls
Print : Prints the logger data to a printer attached to the computer.
Save : Saves the logger data to a file on the computer.
Actuator Controls - Available to Write and Administrator user levels only
Open : Command to open the valve fully.
Stop : Command to stop the actuator in its present position.
Close : Command to close the valve fully.
ESD : Command to put the valve in its Emergency Shut Down position. (This can
be ‘stayput’ or move to either the open or closed position).
Pos DV : A slider control that is used to generate a setpoint position (Desired Value)
for the valve in the range 0 - 100%.
All the controls have a confirmation pop-up, so that the action has to be confirmed before it
takes place. Web page control must be enabled for these controls to work.