Diagnostics and Troubleshooting CDHD
262 User Manual
L5 Softw a re Negative Lim it Sw itch is Tr ipped
L5 Displayed in sequence
D e finit ion Soft ware Negative Lim it Switch is Tripped
Type Warning
Act ive disa ble Not Applicable
M e ssage # WRN 19
Descr iption
Negat ive software limit switch is activated.
PFB < POSLI MNEG and
POSLI MMODE = 1
Action required
L6 Softw a re Lim it Sw itches ar e Tripped
L6 Displayed in sequence
D e finit ion Soft ware Lim it Swit ches are Tripped
Type Warning
Act ive disa ble Not Applicable
M e ssage # WRN 20
Descr iption
Positive and negat ive software lim it switches are
act ivated.
PFB > POSLI MPOS and
PFB < POSLI MNEG and
POSLI MMODE = 1
Act ion required
n STO W arnin g
n Lit steadily
D e finit ion STO Warning
Type Warning
Act ive disa ble Not Applicable
M e ssage # WRN 1
Descr iption The STO signal is not connected when drive disabled.
Action required Check that the STO connector (P1) is wired correctly.