Diagnostics and Troubleshooting CDHD
286 User Manual
t 1 Pow er Sta ge Over- Te m pe r a tur e
t1 Displayed in sequence
D e finit ion Power St age Over-Tem perature
Type Fault
Act ive disa ble Yes
M e ssage # FLT 10
Descr iption
The t em peratur e on the power board has exceeded the
preset limit.
This fault disables the drive.
Action required
Check if t he am bient tem perature exceeds t he drive
specification. Otherwise contact Technical Support.
t 2 I nte grated Pow er Module Ove r - Te m pe ra t ur e
t2 Displayed in sequence
D e finit ion I nt egrated Power Module Over- Tem perature
Type Fault
Act ive disa ble Yes
M e ssage # FLT 39
Descr iption
The t em peratur e within the integrated power module has
exceeded the preset limit.
This fault disables the drive.
Action required
Check if t he am bient tem perature exceeds t he drive
specification. Otherwise contact Technical Support.