Mounting and installation of the compact control panels
Fire brigade periphery module [DE]
5
129 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.13.2.3 X5 fire brigade key depot
Pin Designation Description
8 Sabotage + Tamper monitoring (+)
7 Sabotage - Tamper monitoring (-)
6 Entriegel + Unlocking (+)
5 Entriegel - Unlocking (-)
4 Riegelkont + Latch contact (+)
3 Riegelkont - Latch contact (-)
2 Heizung + Heating (+)
1 Heizung - Heating (-)
Admissible cable cross-section: 0.2…1.5 mm²
1* Door contact
2* Drill protection
3* Key contact
5
6
X5
Entriegel -
Entriegel +
7
8
Sabotage -
Sabotage +
1
2
Heizung -
Heizung +
3
4
Riegelkont -
Riegelkont +
2.2k
Ω
-
+
-
+
-
+
-
+
5
6
7
8
10
1
2
1*
2*
3*
5 W