Mounting and i
nstallation of the compact control panels
Installing an Ethernet switch (modular) FN2012
5
145 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
Types of installation
The small mounting bracket is intended for installation in an empty housing and
can be installed on both sides, i.e., in either the left or the right installation
position. The bracket must be rotated 180 degrees to fit it on the right-hand
side.
The small mounting bracket must be mounted on the left-hand side if it is being
installed in a station inside the Comfort housing.
The large mounting bracket is intended for installation in a station inside a
Large housing – where it has to be mounted on the right behind the power
supply – or for installation in a 19" pedestal housing – where it can be mounted
on the right- or left-hand side wall.
Installation
Please pay attention to the amount of space required for the wiring. The
connections for the optical fibers must be aligned so they point upward.
Small mounting bracket, left-hand
installation position
Large mounting bracket, right-hand
installation position
1 2x/3x fixing screws for DIN rail
2 Retaining bracket for fixing the FN2012 on the side
3
U-rail L=65 mm for small mounting bracket and L=150 mm for large mounting
bracket
4 Mounting bracket
1. Use the two or three screws (1) to mount the U-rail (3) and the retaining
bracket (2) on the mounting bracket (4) as shown.
2. Mount the mounting bracket (4) in the relevant housing as described in the
following chapters.
3. Mount the FN2012 according to chapter 'Installing Ethernet switch FN2012'.
4. Wire up the FN2012 according to chapter 'Wiring'.
1
3
4
2
1
3
2
4