Mounting and installation of the compact control panels
Sounder module
5
200 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.25.2.3 X3 sounder 3 and 4 outputs
Pin Designation Description
1 S4 out+ Sounder output 4 (+)
2 S4 out- Sounder output 4 (-)
3 S3 out+ Sounder output 3 (+)
4 S3 out- Sounder output 3 (-)
Admissible cable cross-section: 0.08…1.5 m
The terminating resistor of 3 kΩ has to be connected even when the output is not in
use.
1
2
X3
S4 out-
S4 out+
3
4S3 out-
S3 out+
+
-
-
+
3 k
Ω
3 k
Ω