Mounting and installation of the compact control panels
RT interface [NL]
5
210 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.27.2.6 X6 relay coils 11…14
Pin Designation Description
4 REL11_IN- Relay coil 11, active low
3 REL12_IN- Relay coil 12, active low
2 REL13_IN- Relay coil 13, active low
1 REL14_IN- Relay coil 14, active low
Admissible cable cross-section: 0.14…1.5 m
5.27.2.7 X7 relay 13 switching contacts
Pin Designation Description
1 REL13_OUT_NO Relay 13 switching contact, normally open
2 REL13_OUT_NC Relay 13 switching contact, normally closed
3 REL13_OUT_CO Relay 13 switching contact, common
Admissible cable cross-section: 0.2…2.5 mm²
5.27.2.8 X8 relay 14 switching contacts
Pin Designation Description
1 REL14_OUT_NO Relay 14 switching contact, normally open
2 REL14_OUT_NC Relay 14 switching contact, normally closed
3 REL14_OUT_CO Relay 14 switching contact, common
Admissible cable cross-section: 0.2…2.5 mm²
NC
NO
1
2
X7
3
CO
REL13_OUT_NO
REL13_OUT_NC
REL13_OUT_CO
NC
NO
1
2
X8
3
CO
REL14_OUT_NO
REL14_OUT_NC
REL14_OUT_CO