Mounting and installation of the compact control panels
Periphery board (2
-
loop)
5
77 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.3.2.3 X7 RT alarm and RT fault changeover contacts
Pin Designation Description
6 FAU_NC RT fault normally closed contact
5 FAU_COM RT fault center tap (common)
4 FAU_NO RT fault normally open contact
3 AL_NC RT alarm break contact (normally closed)
2 AL_COM RT alarm center tap (common)
1 AL_NO RT alarm make contact (normally open)
Admissible cable cross-section: 0.2…1.5 mm²
1 Remote transmission
FAU_ Diagram of relay in normal operation = contact 5/4 closed
AL_… Diagram of relay in normal operation = contact 2/3 closed