Mounting and inst
allation of the compact control panels
Periphery board (4 loops)
5
87 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.4.2.7 X12 / X22 detector line loop 2 (module 2/3)
Pin Designation Description X12 X22
1
4 LOOP1_2– Loop 1 / stub 2 (–) Connection 2nd Loop Connection 4th Loop
3 LOOP1_2+ Loop 1 / stub 2 (+) Connection + 2nd Loop Connection + 4th Loop
2 LOOP1_1– Loop 1 / stub 1 (–) Connection 2nd Loop Connection 4th Loop
1 LOOP1_1+ Loop 1 / stub 1 (+) Connection + 2nd Loop Connection + 4th Loop
Admissible cable cross-section: 0.2…1.5 mm²
1
Loop number without loop extension
The technical term LOOP 2 applies to both loops on connectors X12 and
X22.
One loop or two stubs can be connected.
-
3
4
+
-
1
2
X12 / X22
LOOP2_1+
LOOP2_1-
LOOP2_2+
LOOP2_2-
+