Mounting and installation of the compact control panels
5
97 |
Building Technologies
5.6.2.3 X2 battery supply and signal lines
Pin Designation Description
8 Battery Detection line (#BATT): Battery fault
7 Not used
6 Mains Detection line (#MAINS): Mains fault
5 Not used
4 Usys + System supply (VSYS+)
3 Usys – System supply (VSYS-)
2 Akku + Battery supply (+), protected with F3
1 Akku – Battery supply (–)
Admissible cable cross-section: 0.2…2.5 mm²
1 Cable tree to periphery board or fire terminal board
7
8
5
6
X2
3
4
Mains
Akku +
VSYS-
VSYS+
Battery
2
1
Usys +
-
+
Usys -
Akku -
#BATT
F3