Loading...
'Detection' task card
'Zone'
11
148 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
The following table shows the properties of the templates along with the event
category and the event text of the message that is generated with an alarm.
Main features and typical application Typical event category Event text
1
'Single, Standard':
Single-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Single, no pre-alarm':
Single-detector dependency
Without 'Pre-ALARM'
' ------General autom. Fire ALARM' 'Autom. FIRE ALARM'
'Single, non-latching alarm':
Single-detector dependency
Without 'Pre-ALARM'
' ------Autom. Fire ALARM,
programmable'
'Autom. FIRE ALARM'
'Single, ALARM sub-system':
Single-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'ALARM sub-system'
'Single, Exting. discharged':
Single-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------Exting. discharged
(Aut. Fire AL.)'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Exting. discharged'
'Single, Exting. pre-alarm':
Single-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------Exting. pre-alarm
(Aut. Fire AL.)'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Exting. pre-alarm'
'Single, Gas alarm':
Evaluation of gas detectors that are
connected via an input
Single-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Gas ALARM'
'Single, Gas warning':
Evaluation of gas detectors that are
connected via an input
Single-detector dependency
With 'Pre-ALARM'
Only local alarming is activated in
'MAIN STAGE'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Gas warning'
'Single, door holders':
Single-detector dependency
Without 'Pre-ALARM'
Only the local alarming is activated in
'MAIN STAGE'
' ------General autom. Fire ALARM' 'ALARM door holders'