11
149 |
Building Technologies
Main features and typical application Typical event category Event text
1
'Single, local ALARM':
● Single-detector dependency
● With 'Pre-ALARM'
● Only the local alarming is activated in
'MAIN STAGE'
● 'PRE-STAGE':
– ' --Pre-ALARM, fire'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Pre-ALARM'
● 'MAIN STAGE':
– 'Autom. local ALARM'
'Multi, standard':
● ↑ Multi-detector dependency
● With 'Pre-ALARM'
● 'PRE-STAGE':
– ' --Pre-ALARM, fire'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Pre-ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, garage':
● Multi-detector dependency
● Without 'Pre-ALARM'
' ------General autom. Fire ALARM' 'Autom. FIRE ALARM'
'Multi, store':
● Multi-detector dependency
● With 'Pre-ALARM'
● Only the local alarming is activated in
'MAIN STAGE'
● 'PRE-STAGE':
– ' --Pre-ALARM, fire'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Pre-ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, 2 det. dependency':
● Multi-detector dependency
● With 'Pre-ALARM'
● 'PRE-STAGE':
– ' --Pre-ALARM, fire'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Pre-ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, ALARM sub-system':
● Multi-detector dependency
● With 'Pre-ALARM'
● 'PRE-STAGE':
– ' --Pre-ALARM, fire'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Pre-ALARM'
● 'MAIN STAGE':
– 'ALARM sub-system'
'Multi, 2 det. dependency II' [AT]:
● Multi-detector dependency
● With 'Pre-ALARM'
● Only the local alarming is activated in
'PRE-STAGE'
● 'PRE-STAGE':
– ' ------Autom. First ALARM'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Autom. FIRST ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, 2 det. dependency III' [CH]:
● Multi-detector dependency
● With 'Pre-ALARM'
● 'PRE-STAGE':
– ' ------Autom. First ALARM'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Autom. FIRST ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Two-zone dependency'
● With 'Pre-ALARM'
● Only the local alarming is activated in
'PRE-STAGE'
● 'PRE-STAGE':
– ' ------Autom. First ALARM'
● 'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
● 'PRE-STAGE':
– 'Autom. FIRST ALARM'
● 'MAIN STAGE':
– 'Autom. FIRE ALARM'
Table 5: Properties of the templates
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.