'Detection' task card
'Zone'
11
149 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
Main features and typical application Typical event category Event text
1
'Single, local ALARM':
Single-detector dependency
With 'Pre-ALARM'
Only the local alarming is activated in
'MAIN STAGE'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Autom. local ALARM'
'Multi, standard':
Multi-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Multi, garage':
Multi-detector dependency
Without 'Pre-ALARM'
' ------General autom. Fire ALARM' 'Autom. FIRE ALARM'
'Multi, store':
Multi-detector dependency
With 'Pre-ALARM'
Only the local alarming is activated in
'MAIN STAGE'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Multi, 2 det. dependency':
Multi-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Multi, ALARM sub-system':
Multi-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' --Pre-ALARM, fire'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Pre-ALARM'
'MAIN STAGE':
'ALARM sub-system'
'Multi, 2 det. dependency II' [AT]:
Multi-detector dependency
With 'Pre-ALARM'
Only the local alarming is activated in
'PRE-STAGE'
'PRE-STAGE':
' ------Autom. First ALARM'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Autom. FIRST ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Multi, 2 det. dependency III' [CH]:
Multi-detector dependency
With 'Pre-ALARM'
'PRE-STAGE':
' ------Autom. First ALARM'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Autom. FIRST ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
'Two-zone dependency'
With 'Pre-ALARM'
Only the local alarming is activated in
'PRE-STAGE'
'PRE-STAGE':
' ------Autom. First ALARM'
'MAIN STAGE':
' ------General autom. Fire
ALARM'
'PRE-STAGE':
'Autom. FIRST ALARM'
'MAIN STAGE':
'Autom. FIRE ALARM'
Table 5: Properties of the templates
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.