5. Leave the 'Delay' parameter for the 'Section' elements or the 'Detection area'
element at '00:00:00' as immediate warning is required on each floor.
6. Use multiselection to select all 'Section' elements or the 'Detection area'
element under the 'Causes ALERT' element and copy these using the 'Copy'
function.
7. In the 'Phased sounder evac control'/'Phased voice evac control' element,
highlight the 'Causes EVAC' element or the 'Causes EVAC FIRE
(+DEGRADED MODE)' element.
8. Use 'Paste' to add the copied 'Section' elements or the 'Detection area' element
to the 'Causes EVAC' element or the 'Causes EVAC FIRE (+DEGRADED
MODE)' element.