Sample configuration for a 2-stage, multi-phase building evacuation
process
w There is a ↑ 'Section' element created for each floor in the 'Hardware' task
card.
w At least one alarm device or sounder of 'PHASED sounder' type is installed on
every floor.
1. Create a 'Phased sounder evac control’ element or a 'Phased voice evac
control' element for floor 2 within the 'Evac control group' element.
2. In the 'Phased sounder evac control'/'Phased voice evac control' element,
highlight the 'Causes ALERT' element.
3. Assign the 'Causes ALERT' element with 'Assign' to all 'Section' elements that
represent a floor. The standard event category for this is ' --All Fire ALARMS'.
Information: Selection of a suitable event category depends on the actual
application. Tip: Assign the corresponding 'Detection area' element if the
'Section' elements are located within a specially created 'Detection area'
element.
4. Highlight the 'Causes ALERT' element.