Configuring an extinguishing reporting zon
16
380 | 412
'Extinguishing reporting zone' – 'Reporting 'pre-alarm'' – properties of
the template
Main features and typical application Typical event category Event text
1
● Monitors the trigger signal for
extinguishing in the relevant
flooding zone
● When extinguishing is triggered,
an alarm is triggered.
' ----Pre-ALARM, extinguishing
released'
NOTICE! This event has an
individual AVC concept which
bridges the global AVC settings
upon occurrence.
'Exting. released'
● Isolation of the flooding zone ' --Other isolation' 'Exting.sector OFF'
● Fault monitoring in the flooding
zone
' --Other fault' 'Extng.sector fault'
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.
'Extinguishing reporting zone' – 'Reporting 'alarm'' – properties of the
template
Main features and typical application Typical event category Event text
1
● Monitors the trigger signal for
extinguishing in the relevant
flooding zone
● When extinguishing is triggered,
an alarm is triggered.
' ------Exting. discharged (Aut. Fire
AL.)'
NOTICE! This event has an
individual AVC concept which
bridges the global AVC settings
upon occurrence.
'Exting. released'
● Isolation of the flooding zone ' --Other isolation' 'Exting.sector OFF'
● Fault monitoring in the flooding
zone
' --Other fault' 'Extng.sector fault'
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.
Creating and configuring the 'Extinguishing reporting zone'
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
w An 'Section' element is created in the 'Detection tree'.
1. Under the 'Section' element, create an 'Extinguishing reporting zone' element
with the required template.
2. Enter the required customer text in the 'Overview' tab.