Configuring an extinguishing reporting zone
16
381 |
Building Technologies
3. Assign a 'Extinguishing sector control' element to the 'Extinguishing reporting
zone' element with 'Assign'.
You will find information on creating and configuring an 'Extinguishing sector
control' element in chapter 'Configuring flooding zone control [➙ 354]'.
'Extinguishing reporting zone' – parameters in the 'Events' tab
The table below shows the adjustable parameters for the following events:
● 'Active | ----Pre-ALARM, extinguishing released'
● 'Active | ------Exting. discharged (Aut. Fire AL.)'
Only one of the events above can occur in the '
All other events do not have any adjustable parameters.
Parameters Value Description
'Custom event text' On/off
Creates an alternative event text, which is displayed
instead of the standard event text.
'Use individual AVC
settings'
On/off
For the 'Extinguishing reporting zone' element, an
alternative ↑ AVC can be defined, which differs from
that in the superordinate 'Detection area'.
You will find information about the AVC parameters
in chapter 'Alarm verification concept (AVC) [➙ 142]'.
See also
2 Configuring flooding zone control [➙ 354]
2 Alarm verification concept (AVC) [➙ 142]